Installation operating Maintenance Instructions Radial roof fan

 Installation, Operating and Maintenance Instructions for Radial Roof Fans

DRH-Minivent

DRH

DRV-Minivent

DRV

DRVF

DRVF-H


Installation, Operating and Maintenance Instructions  for Radial Roof Fans

 Installation, Operating and Maintenance Instructions for Radial Roof Fans

DRH-Minivent

DRH

DRV-Minivent

DRV

DRVF

DRVF-H


1. Introduction

These installation, operation and maintenance directions (IOM) square measure

intended to be studied, understood and ascertained all told points by people who square measure

in charge of the Turbo – Lufttechnik Radial Roof Fan. Especially

important details for victimization the fan square measure one by one identified in these

instructions. the entire IOM thus ought to be scan once planning the

complete plant. thus the IOM square measure already connected to our order

confirmation. One copy ought to be unbroken close to the fan

The IOM ought to be created offered to any or all people that are accountable of the

fan. If they apprehend them well, in operation faults are often avoided and a troublefree

operation is bonded.

We suggest to scan the IOM rigorously before startup. we have a tendency to shall not be

liable for damages and breakdowns ensuing from the non-observance of

IOM's!

If any difficulties arise, please contact our business house in dangerous Hersfeld or

one of our technical advisers within the field.

We reserve all rights concerning the contents of those IOM's and technical

changes for technical improvement of our fans.

2. vary of application

Our radial roof fans were designed consistent with the state of the art and square measure

operationally reliable. they're subject to a top quality check and experimentation within the

factory and leave it in good condition. (Look at the management card connected

to the fan within the service bag)

The fan has completely been designed for traditional and cool air.

Any other application isn't as directed. accidental or improper use will lead

to risk for the user or third persons, and cause serious injury to the machine.

The risk is on the user's aspect.

This image beside the text of this IOM points to things wherever a

danger to life and limb of persons exists. Please observe the

instructions.

This image points to directives, rules and directions that square measure

important to the protection of the machine and alternative plant elements as

well because the correct sequence of the operations.

This image refers to tips for application and particularly helpful info.

They help you to optimally use your fan.

Installation, startup and maintenance of fans

Measurement, analysis and analysis of all information vital to the

operation (e.g.: Pressure, volume, unpitched sound, vibrations etc.)

balancing

spare elements service

Our staff guarantee skilled installation and startup of your fans.

Our technical advisers within the sales force and our field workers offer

individual recommendation to you and assist you if you wish to put orders.

4. Safety at work

The following directions for safety at work should be particularly ascertained :

The user needs to make certain that solely qualified workers work with the fan.

Necessary works might solely be administrated by properly trained workers, with

sufficient expertise and data of the relevant standards,

specifications, rules for interference of accidents and in operation

conditions. they need to be appointed by the person being chargeable for

the safety of the plant.

Among others they conjointly ought to have data regarding aid and native

rescue instrumentality.

The operator should commit himself to work the fan solely in a wonderful

condition.

Any person being accountable of assembly, activity, startup, operation and

maintenance of the fan got to have scan and understood the entire

IOM's.

One should make certain that no foreign objects (tools etc.) and water square measure in

the fan housing.

Before the primary experimentation you've got check if mechanical and electrical

protecting devices were properly put in.

If the fan is shipped while not protective devices the user needs to make certain

that they're mounted. protective devices not meeting DIN twenty four 617

standard got to be thought of as residual endangering.

After assembly or maintenance of the electrical installations, the

protective measures applied square measure to be tested (e.g.:earthing resistance).

Never bit the fan wheel whereas the fan is running.

In case of any malfunction, the fan is to be shifted right away, and

the reason behind the malfunction is to be known and eliminated.

Unauthorized modifications and changes effecting the protection of the fan square measure

prohibited.

Before beginning maintenance works the fan needs to be shifted and

secured with a lock to forestall unauthorized shift in. Protection

devices might solely be removed if the fan is out of action.

For all sorts of labor on the fan, as a rule it's to be out of action. The

impeller needs to be fast to forestall turning.

After repair works you've got to envision before beginning the fan, if all

protection devices were reinstalled.

5. Transport

The native safety rules apply to the transport of the fan in any case.

Avoid shocks by all means that throughout transport.

You have to form certain that the fan cannot slip and tilt.

To avoid damages caused by forced rupture and careless loading or unloading,

transport needs to be administrated rigorously and cautiously.

While unloading the fan, it should not be set down too roughly, since this will

lead to deformations of the blade, the housing, and damages of the motor

bearing.

We suggest you to go away the

appliance within the original packing till

the place of installation is reached, in

order to avoid any injury thanks to

transport.

Inclination angles of quite 60°

are impermissible.

The hoisting instrumentality and means that of transport used should be

designed for the load of the fan.

6. Scope of delivery

8. Construction options

Radial roof fans within the ten styles

Design DRH / DRH Minivent

with horizontal air exit and external rotor

motor.

Design DRVF-I

like kind DRVF, however in addition with noise

protection lining within the housing.

Design DRV / DRV-Minivent

with vertical air exit and external rotor motor.

Design DR-SDH

like kind DRH, however with horizontal air exit

through a spherical sound absorbent on the outlet

side.

Design DRVF

with vertical air exit and IEC commonplace motor

placed outside of the flow.

Design DR-SDV

like kind DRV, however with vertical air exit

through a spherical sound absorbent on the outlet

side.

Common construction details:

• Mounting base with influx nozzle and motor fastening plate manufactured from torsion

resistant zendzimier galvanized steel sheet

• Housing manufactured from Al-sheet metal

• Connecting flanges in keeping with DIN 24154, row 3

• Radial vane, one-side suction, dynamically balanced in keeping with ISO 1940,

quality grade G six.3, in welded version with powder coating, shade of color RAL

7030

(The impellers of the sizes 224 and 250 ar manufactured from galvanized steel sheet)

Motors for DRH- and DRV-Minivent, DRH and DRV 224E, additionally as DRH-E

and

DRV-E have a single-phase A.C. electrical condenser motor in external rotor motor

version and within thermal contacts, closed kind with moisture-proof and

tropics-proof insulation.

Application: For a blower output of liquid ecstasy. 40°C.

The types DRH and DRV 250 - 710

are equipped with rotary current or A.C. motors in external rotor motor

version, closed kind , with thermal contacts LED outward and with moistureproof

insulation

Application: For a blower output of liquid ecstasy. 40°C.

Motors for the styles DRVF and DRVF-H

The fan includes a rotary current-standard motor in keeping with ICE-standard in style

V1 while not thermal contacts

which is placed outside the blower output.

Application: kind DRVF

For a blower output of liquid ecstasy. 40°C.

Design DRVF-H

For a blower output of liquid ecstasy. 120°C in continuous operation:

• The devices ar fitted as normal with repair switches mounted on the skin of

the housing.

Conduit boxes will be delivered upon request.

9. Switch, motor protection

The external rotor motors of our radial roof fans ar, with the exception of the

explosion-proof varieties, equipped with thermal contacts.

The rim motors of the series DRVF and DRVF-H will be delivered with thermal

contacts, if desired.

These temperature-dependent management parts ar directly embedded into the coil

winding heads of the motors.

The switch capability is: four A at cos. = 0.6 250 V fifty cycle

6.3 A at cos. = 1.0 250 V fifty cycle

The thermal contacts shield the motor winding against overload (e.g. part failure, over

and beneath voltage, unduly high close temperature and high switch frequency).

To reach AN optimum protecting result, the thermal contacts should be switched into the

control line of the most contactor or the management switch.

When the contacts have responded, a restart could solely be applied by hand. this method

of protection is warranted with our BV-motor full protection mixtures.

In case of unskilled association or failure to use our switch devices, no pledge

will be given to the client.


The explosion-proof varieties and also the DRVF / DRVF-H - motors should be protected by AN

overcurrent protecting gear with current-dependently delayed triggering in keeping with the

valid

VDE rules.

The thermorelays of the motor protection ar to be adjusted to the several nominal

current of the motor.

Concerning the explosion-proof devices, we propose putting in the protecting switch

outside the unsafe location, since otherwise AN explosion-proof switch should be used.

An switch or a two-stage switch is comfortable for the Minivent kind.

10. Technical info

Performance curves will solely be unbroken if the fan has optimum influx.

11. Erection and assembly

The valid laws, standards, rules, directives etc. are to be

observed.

The fans ar appropriate for installation on the roof (in the open air).

Height of roof base should be a minimum of 350 millimeter.

They can be put in as freely uptake fans, or be connected to pipelines.

If a lover is mounted with the suction aspect on a pipeline, a compensating

piece (elastic association piece) is to be put in (stress-free installation).

We can provide in depth accessories for all fans.

Please see our catalog for it, or contact our technical advisers within the field

in the mill at unhealthy Hersfeld.

All radial roof fans ar delivered in ready-to-mount condition.

The installation will be applied simply and quick, if the subsequent points a

observed:

1. the bottom should be horizontal and even, and have sleek borders.

A waterproofing strip is to be inserted between the bottom edge and also the

foundation plate.

The devices of the categories DRH ANd DRV will be mounted with an

inclination of up to 20° .Twisted installation should be avoided, since

otherwise the vane cannot run freely, and scrapes the influx nozzle

The measurements of the bottom ar to be gathered from the corresponding

pages of our catalog .

2. To avoid undesirable condensation on the within of the bottom plate, we

recommend insulating it.

3. Fastening is applied by means that of four polygon insane. For waterproofing, always

4 leaden waterproofing washers and four Korrex protective caps ar closed in in th

attached bag.

4. whereas mounting automatic waterproofing caps on the sound absorbent base one

must observe that the flap shaft is in parallel with the connecting links.

Important notes for the installation of our fans

For maintenance and repair works one should guarantee unobstructed access to th

fan at any time.

Therefore the subsequent has got to be observed:

1) The fan should be accessible and dismountable while not excessive

expenditure of labor. what is more there should be comfortable clear area

around the fan to hold out maintenance works.

2) Our pledge when components replacements or repair works won't cowl

additional prices caused by the nonconformity of item 1; these are

charged to the client.

Electrical association

Connection has got to be created by AN skilled worker in keeping with VDE rules

Observe the indications on the nameplate!

Compare mains voltage!

The motor is to be connected in keeping with the closed in association diagra

(motor management card).

If cable entries within the passage box or repair switches don't seem to be used, they hav

to be rigorously fastened to stop dirt and wetness from getting into the

conduit box. Tighten all contact screws and insane properly, to avoid too hig

transition resistance.

Screwed cable glands have to be compelled to be equipped with pull-relief.

• the doorway of the feeding cables into the passage box or the repair

switch, from below or from the aspect, severally, should be applied

impermeably to water.

All roof fans (except for the KDRVF sorts and Eexe II T 3-devices) area unit

fitted as normal with repair switches that perform the emergency stop

function and absolutely suits the laws consistent with VDE 0113 -

IEC 204 and VBG four, as a result of their outside and freely accessible

arrangement in addition as their special instrumentality (e.g. for 3-lock interlocking

device, ZLT connecting chance etc.).

The electrical association to the repair switch (or the passage box,

respectively.) might solely be distributed by associate degree skilled worker. Please observe th

connection diagram of the control card connected to each device

here.

The values measured on the spot should be entered within the management card.

The driving motors area unit delivered for the subsequent voltages:

1. Rotary current-motors, with a speed (also ex-proof) for 230/400 potential unit.

The electrical association is distributed to associate degree operative voltage of

230 potential unit for delta association, associate degreed to an operative voltage of four hundred potential unit

for star association.

Motors for different operative voltages should be ordered individually.

2. Rotary current-motors, pole-changing consistent with Dahlander: for four hundred

Volt operative voltage. These motors area unit equipped with a double star-st

winding.

Motors for operative voltages aside from four hundred potential unit should be ordered

Separately

Installation, Operating and Maintenance Instructions for Radial Roof Fans DRH-inivent DRH DRV-Minivent DRV DRVF DRVF-H DR-SDH KDRVF

Rotary current-motors, with 2 separate windings: for four hundred potential unit

operating voltage. Motors for operational voltages aside from four hundred potential unit

must be ordered on an individual basis

4. A.C. motors, for 230 potential unit.

5. Radial roof fans of the Minivent kind area unit equipped with A.C. motors fo

230 Volt.

6. All driving motors of the radial roof fans DRH and DRV area unit

maintenance-free. Regreasing is senseless.

Arrangement of the passage box or

the repair switch, severally

 

Figure 1

Fastening by suggests that of associate degree

anchor bolt of the roof fan

 

Figure 2

Fastening at the aspect on the

folded back flat solid, holes

are out there

 

Figure 3

Fastening on the roof base

12. experiment / startup

BEFORE beginning THE experiment and also the INITIAL

OPERATION, IN ANY CASE OBSERVE THE SECTION SAFETY AT

WORK once more.

One should proceed as follows:

Before starting-up the radial roof fan you've got to form certain that no foreign

objects (tools, dirt etc.) were left in it.

-Check if all screw joints area unit tight.

For open recess and outlet a guard should be mounted. make certain it's.

The connecting items on the suction aspect yet because the whole passage system

must be fully mounted.

After having connected the fan motor you've got to ascertain by quickly switch

on and off if the motor turns to the right direction:

When trying from the motor aspect the motor needs to communicate the left. (If you

look from the recess of the vane, it's to show to the right). The direction

of rotation should be identical as indicated by the arrow.

If the direction of rotation is wrong, the poles of the motor got to be

changed.

(change phases within the repair switch, the passage box or the switch cupboard.)

The vane should on no account scrape the influx nozzle.

Measure the present absorption of the motor and compare it with the GHB.

current consumption on the plate.

The impellers of our fans were balanced consistent with ISO 1940 quality G half-dozen.3.

Since, thanks to the system, the fan will be excited to start out moving once its

installation, one should make certain that a vibration-damped operation according

to VDI 2056 machine cluster T is bonded once the fan is ready into operation.

This particularly applies to fans with many speeds or variable speed, where

vibrations got to be measured over the whole speed vary.

13. Breakdown of the operations

If vibrations arise within the curse of your time, they'll have the subsequent reasons:

a) Caking has shaped on the blades of the vane.

Remedy: Clean vane, retighten the screws.

b) The vane is full of influence of corrosion.Remedy: Clean and

rebalance the vane, unless heavily unsound. Retighten the screws.

Further malfunctions which can arise

c) Fan doesn't work.

Remedy: check power provide, check motor

d) vane scrapes another surface.

Remedy: examine the vane space for foreign objects, check motor

fastening.

e) Motor protection is discharged throughout ventilating operation or experiment.

Remedy: Check if the motor turns laborious (bearing and winding damaged),

check power provide.

Fan doesn't reach its practical performances demanded.

Remedy: Clean vane, check passage system (are all flaps open?), have

any changes been created within the passage system?

14. General maintenance

In regular intervals, however a minimum of once a year, the fan ought to be checked by a

specialized company.

Test things are: correct functioning

Readiness for service

Bolted connections

Vibration-damped run

Motor/current consumption (see section maintenance,

motor)

If needed, the fan needs to be cleansed, maintained and repaired.

If the fan isn't continuously used, it's to run a minimum of

1 hour each two months around. this can be vital, as a result of the motor

bearings suffer if not used for a protracted time.

All examinations yet as maintenance and repair works ought to be

recorded during a take a look at book.

15. Description of the vane

You can notice an in depth description of the vane and of the motor on page seven.

Replacement of rotor set

If the rotor set should be changed, the subsequent order is to be observed:

a) Current provide from the building to the fan is to be disconnected.

b) Motor cable is to be disconnected.

c) Outside and within overlay should be removed.

d) Motor fastening is to be detached from stud bolts.

e) Motor plate with motor and vane is to be taken out.

f) Complete unit is to be came back - freight paid - to the producing

company.

Reinstallation of the impeller:

- One should make certain that motor and vane don't seem to be separated.

- Before beginning the fan one should check whether or not the vane will be simply

revolved by hand, and doesn't scrape the other surface.

Maintenance of the motor

The motor bearings area unit life-greased. they're full of a special grease within the

manufacturing company. The service lifetime of this grease is ten 000 to twenty 000 h.

After any more break, it's advisable  to hold out associate degree scrutiny of the

bearings before beginning. this is applicable to bran-new motors, as well.This is

especially vital if noises occur, thanks to congealment of the grease within the

bearing.

Also talk to the assembly, operational and maintenance directions of the

motor manufacturer.

(Please request on an individual basis, if needed.)

17. Storage of spare components

All spare and carrying components that can't be provided at intervals a brief amount of

time ought to be taken available. Production losses area unit sometimes dearer

than the prices of such a relation.

We would prefer to indicate notably, that spare components not provided by USA area unit

were not checked and discharged by USA. The manufacturer shall not be to blame for

damages caused by the utilization of not original components and accessories.




Tuesday, December 22, 2020

Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature

 Technical data sheet Damper actuator Modulating damper actuator Duct sensor for relative humidity and temperature

Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature
Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature 


Damper actuator for operating air control dampers in ventilation and air-conditioning systems for

building services installations

• For air control dampers up to approx. 4 m2

• Torque 20 Nm 

• Nominal voltage AC/DC 24 V

• Control: modulating DC 0 ... 10 V, position feedback DC 2 ... 10 V Technische Daten

Electrical data Nominal voltage AC 24 V, 50/60 Hz

DC 24 V

Nominal voltage range AC/DC 19.2 ... 28.8 V

Power consumption In operation

At rest

For wire sizing

2 W @ nominal torque

0.4 W

4 VA

Connection Cable 1 m, 4 x 0.75 mm2

Functional data Torque (nominal torque) Min. 20 Nm @ nominal voltage

Control Control signal Y

Working range

DC 0 ... 10 V, typical input impedance 100 kΩ

DC 2 ... 10 V

Position feedback (Measuring voltage) DC 2 ... 10 V, max. 1 mA

Position accuracy ±5%

Direction of rotation Reversible with switch 0 / 1

Direction of rotation at Y = 0 V at switch position 0 resp. 1

Manual override Gearing latch disengaged with pushbutton,

self-resetting

Angle of rotation Max. 95° , limited on both sides

by means of adjustable, mechanical end stops

Running time 150 s

Sound power level Max. 45 dB (A)

Position indication Mechanical, pluggable

Safety Protection class III Safety extra-low voltage

Degree of protection IP54 in any mounting position

EMC CE according to 89/336/EEC

Mode of operation Type 1 (to EN 60730-1)

Ambient temperature range –30 ... +50°C

Non-operating temperature –40 ... +80°C

Ambient humidity range 95% r.H., non-condensating (EN 60730-1)

Maintenance Maintenance-free

Dimensions / Weight Dimensions See «Dimensions» on page 2

Weight Approx. 1’050 g

Safety notes

The damper actuator is not allowed to be used outside the specified field of applica tion,

especially in aircraft or any other form of air transport.

• Assembly must be carried out by trained personnel. Any legal regulations or regulations

issued by authorities must be observed during assembly.

• The device may only be opened at the manufacturer‘s site. It does not contain any parts

that can be replaced or repaired by the user.

• The cable must not be removed from the device.

• When calculating the required torque, the specifications supplied by the damper

manufacturers (cross section, design, installation site), and the air flow conditions must

be observed.

• The device contains electrical and electronic components and is not allowed to be disposed

of as household refuse. All locally valid regulations and requirements must be observed.

Modulating damper actuator AC/DC 24 V, 20 Nm

Product features

Mode of operation The actuator is controlled by means of a standard control signal DC 0 ... 10 V. It opens to the

position dictated by this signal. The measuring voltage U allows the damper position (0 ... 100%)

to be electrically indicated and serves as a follow-up control signal for other actuators.

Simple direct mounting Simple direct mounting on the damper spindle with a universal spindle clamp, supplied with

an anti-rotation strap to prevent the actuator from rotating.

Manual override Manual operation is possible with the self-resetting pushbutton (the gearing latch remains

disengaged as long as the pushbutton is pressed).

Adjustable angle of rotation Adjustable angle of rotation with mechanical end stops.

High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the

end stop is reached.

Accessories

Description Data sheet

Electrical accessories Auxiliary switch S..A.. T2 - S..A..

Feedback potentiometer P..A.. T2 - P..A..

Range controller SBG24 T2 - SBG24

Positioner SG..24 T2 - SG..24

Digital position indication ZAD24 T2 - ZAD24

Mechanical accessories Various accessories (clamps, shaft extensions etc.) T2 - Z-SM..A..

Electrical installation

Wiring diagrams

Y

U

1 2 3 5

DC 0…10 V

DC 2…10 V

– +

~ T

Dimensions [mm]

Dimensional drawings

139

56

64

30 109 41

88

Damper spindle Length

Clamp on top min. 42 10 ... 20 (26.7)

Clamp on bottom min. 20 10 ... 20

Notes

• Connection via safety isolating transformer.

• Other actuators can be connected in parallel.

Please note the performance data.

Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature

Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature


Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature

Technical data sheet Damper actuator motorized damper install


Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature

Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature

Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature
Technical data sheet Damper actuator motorized damper install Duct sensor for relative humidity and temperature


Duct sensor for relative humidity and temperature

EN Datasheet


Subject to technical alteration

Issue date 2007/01/27


Duct sensor for relative humidity and temperature

Application
Duct sensor for measuring relative humidity and temperature in gaseous
media of heating, cooling and airconditioning
systems (e.g. in fresh air/
exhaust air ducts). Designed for locking on control and display systems.
Additionally, the device can be supplied with a passive temperature sensor
e.g. PT100, PT1000, NTC10k etc.
Types Available
LCNFTK140VV
Duct sensor 140mm, output 0...10V,
with transducer for temperature, output 0...10V
LCNFTK270VV
Duct sensor 270mm, output 0...10V,
with transducer for temperature, output 0...10V
LCNFTK400VV
Duct sensor 400mm, output 0...10V,
with transducer for temperature, output 0...10V
Norms and Standards
CEConformity:
89/336/EWG Electromagnetic compatibility
Standards: EN 607301:
2000
EN 6100042
EN 6100043
EN 6100044
EN 6100045
EN 6100046
EN 55022B
Technical Data Hardware
Power supply: 1524VDC/
24AC +/10%
Power consumption: typ. 0,5W / 1,7VA
Measuring range: Humidity: 0...100%rH
Temp. 20...+
80°C
Output: Humidity: 0...10VDC, load: min. 5kOhm
Temp.: 0...10VDC, load: min. 5kOhm
(Optional Type VS: Resistance NTC/PTC)
Clamps: Terminal screw max. 1,5mm²
Mounting length L: 140mm/270mm/400mm
Sensor pipe: Material PA6, colour black
Filter element: Material stainlesssteel,
mesh size 80μm
Connection head: Material PA6, colour white
Protection: Connection head IP65
Cable entry: Single entry M16 for cable max. D=8mm
Ambient temperature: 20...+
70°C
Accuracy
Temperatur, absolute Genauigkeit
Temperature, absolute accuracy
±0°C
±1°C
±2°C
±3°C
20°
C 10°
C 0°C 10°C 20°C 25°C 30°C 40°C 50°C 60°C 70°C 80°C
Mounting Advice
The sensor is directly mounted to the ventilation duct by means of a
mounting flange or by screws.
Please also note our general remarks in our INFOBLATT THK.
Duct sensor for relative humidity and temperature

Electrical connection
The devices are constructed for the operation of protective low voltage
(SELV). For the electrical connection, the technical data of the
corresponding device are valid. Specially with regard to passive sensors
(e.g. PT100 etc.) in 2wire
conductor versions, the wire resistance of the
supply wire has to be considered. Probably, the same has to be
compensated by the following electronics. Due to the selfheating,
the wire
current affects the accuracy of the measurement. Thus, the same should
not exceed 1mA.
Application Notice
Due to air circulations dirt and dust particles can be piled up in the
course of time on the sintered filter which is protecting the sensor.
Thus, the function of the sensor can be affected. After having
dismantled the filter, the same can be cleaned by blowing it out with oilfree
and filtered compressed air, superclean
air or nitrogen or by
washing it out with distilled water. If the filter is too dirty, the same
should be replaced.
Refrain from touching the sensitive humidity sensor. Any touch of the
same will result in an expiration of the warranty.
When using the sensor in aggressive gases, an early recalibration or a
change of the humidity sensor can become necessarily. Such a
recalibration or a probable sensor change do not come under the
general warranty.
Optional Accessories
(MF19PA)
Mounting flange for installation on ventilation duct
Mounting flange for installation on ventilation duct

Mounting flange for installation on ventilation duct


Thursday, December 17, 2020

HOW TO OPERATE Cool Air Center

 O P E R A T I N G  D E S C R I P T I O N Cool AirCenter

Main Switch, Phase lights, Control voltage 220 V and control fuses,  Operating or fault indication, Voltage Supply Axicos, Collective fault signal, Ventilation Technical Directions, Requirements for the operation of the ventilation system, Filter monitoring, Demand supply air and exhaust air, night cool control
Main Switch, Phase lights, Control voltage 220 V and control fuses,  Operating or fault indication, Voltage Supply Axicos, Collective fault signal, Ventilation Technical Directions, Requirements for the operation of the ventilation system, Filter monitoring, Demand supply air and exhaust air, night cool control


General Directions

Main Switch

The main switch is to be switched on before commissioning commences.

Further functions:

1. Switching off of the complete system in the event of danger.

2. Switching off when work is being performed on the electrical installation, or when work is

being carried out inside the control switchboard.

Phase lights L1 - L2 - L3 (with light prefuse)

In order to operate the system, voltage must be present in all 3 phases.

Should the supply to a phase fail, the motor protection overcurrent relays for the drive motors are

actuated and switch the control system to fault.

When the 3 phases are restored, before starting up again, the motor protection equipment must

be switched to the working position by pushing the keys.

Control voltage 220 V and control fuses

For safety reasons the control voltage is produced by the isolating transformer.

The transformer is protected against overloading and short circuiting by fuses.

Should the complete control system fail, the fuses should be checked.

For the control circuit supply air and exhaust air different fuses are used.

In case of a fault the fuses have to be checked.

Operating or fault indication

The operating status of each motor that is switched on is indicated by the control panel. Should

a fault occur in the motor control e.g. through the actuating of an over current relay or a thermal

contact in the motor winding this is shown as a blinking signal and written into the alarm list of the

panel.

Main Switch, Phase lights, Control voltage 220 V and control fuses,  Operating or fault indication, Voltage Supply Axicos, Collective fault signal, Ventilation Technical Directions, Requirements for the operation of the ventilation system, Filter monitoring, Demand supply air and exhaust air, night cool control


Control voltage 24 V

The low voltage that is necessary for the signal lamps and the PLC-terminal strip is produced by a

power supply. The power supply is protected against overloading and short circuiting by fuses.

In the event of fault the prefuse on the primary side and the fuses on the secondary side should be

checked.

Voltage Supply Axicos

The PLC-station has its own power-supply unit with an input voltage of 230V. It is protected by

fuses.

Collective fault signal

The individual fault signals are, as explained, shown on the control switchboard with the help of

the control panel, and in addition collected in the PLC-station and given out as a PLC collective

fault signal.

The collective fault signal is wired onto an electric terminal and is available for further signal

transmission.

Main Switch, Phase lights, Control voltage 220 V and control fuses,  Operating or fault indication, Voltage Supply Axicos, Collective fault signal, Ventilation Technical Directions, Requirements for the operation of the ventilation system, Filter monitoring, Demand supply air and exhaust air, night cool control
Main Switch, Phase lights, Control voltage 220 V and control fuses,  Operating or fault indication, Voltage Supply Axicos, Collective fault signal, Ventilation Technical Directions, Requirements for the operation of the ventilation system, Filter monitoring, Demand supply air and exhaust air, night cool control


Ventilation Technical Directions

1. Requirements for the operation of the ventilation system

Before starting operation the following points should be checked:

All the covers, revision ports and access openings on the aeraulic equipment must be

hermetically closed.

The control units as well as the covers of all electrical equipment must be closed.

2. Filter monitoring

Main Switch, Phase lights, Control voltage 220 V and control fuses,  Operating or fault indication, Voltage Supply Axicos, Collective fault signal, Ventilation Technical Directions, Requirements for the operation of the ventilation system, Filter monitoring, Demand supply air and exhaust air, night cool control
Main Switch, Phase lights, Control voltage 220 V and control fuses,  Operating or fault indication, Voltage Supply Axicos, Collective fault signal, Ventilation Technical Directions, Requirements for the operation of the ventilation system, Filter monitoring, Demand supply air and exhaust air, night cool control


The air filters in the supply air units are monitored with the help of a differential pressure switch.

As the dirt in the filters increases, the differential pressure rises so causing the diffential

pressure switch to activate a signal in the PLC station. This is then passed further on over the

collective fault signal.

Attention is also drawn to the dirtying of the filter by way of a visual reading instrument. The

filter should be changed by a pressure difference of approx. 200 Pa.

Control and regulation in the PLC programme:

Demand supply air and exhaust air

The system is switched with the control switch to ON / OFF or READY FOR OPERATION.

Control switch with the positions:

2 = AUTOMATIC / remote control

The supply ventilators and the exhaust air ventilators are free to operate.

By time clock operation automatic the system will be switched on and off by way of the

Axicos PLC-Station.

0 = OFF

1 = MANUAL (ON)

The supply air ventilators and exhaust air ventilators are switched ON directly.

Main Switch, Phase lights, Control voltage 220 V and control fuses,  Operating or fault indication, Voltage Supply Axicos, Collective fault signal, Ventilation Technical Directions, Requirements for the operation of the ventilation system, Filter monitoring, Demand supply air and exhaust air, night cool control


Demand the complete system

a) In the simplest case by way of an external (potential free) contact of the printing machine.

Result: When the printing machine is running the ventilation system also functions.

b) In addition to the the printing machine contact, the ventilation system can be switched on in

combination with the external selector switch. This is carried out by way of the position

HAND in continuous operation, or the position A ( A = Automatic), by way of a time

programme contained in the DDC-programme (time dependent ON / OFF).

Operation: night cool control

The method of operation is only effective when the ventilation system from the normal operating

demand is switched to the OFF function.

This auxillary operation is intended for cooling the warm air in summer time by way of ventilation

operating at night. The low temperature outside air is used to remove the remaining room heat

caused by daytime working. This results in the room being cooled down.

The night cooling system switches on under the following conitions:

Room temperature in excess of room temperature set point + 3°C

The difference between inside and outside temperature must be more than 3K

Night switching time is between 22 p.m. and 6 a.m.

The above conditions are programmed in the PLC-station , however they can be altered at any

time.

With this auxillary operation the supply air temperature base, which is dependent upon the room

temperature, is changed over to a low temperature niveau, to enable ventilation (cooling) with the

highest possible percentage of outside air.

Supply air temperature base by normal operating = +19...26°C

Supply air temperature base by night cooling operation = +17…24°C

 

Wednesday, December 16, 2020

Cool AirCenter, Installation of the roof outside air exhaust air Installing air column Duct

i.Cool AirCenter, Installation of the roof ducts for outside air and exhaust air, pitch of the roof, Installing the air column, Duct installation, Installing the control cabinet, 

i.Cool AirCenter, Installation of the roof ducts for outside air and exhaust air, pitch of the roof, Installing the air column, Duct installation, Installing the control cabinet,
i.Cool AirCenter, Installation of the roof ducts for outside air and exhaust air, pitch of the roof, Installing the air column, Duct installation, Installing the control cabinet, 


INSTRUCTIONS FOR TRANSPORTING AND INSTALLING

i.Cool AirCenter

1. Installation of the roof ducts for outside air and exhaust air

a) Below the roof of the hall, install a replacement of steel girders to hold the roof base

(weight), according to the instructions of the engineer who made the static calculations.

b) A roofer should cut out the gap in the roof according to the existing detail plans.

c) Place the roof base in the middle of the gap and use Parker screws to fasten the supporting

flange to the roof.

d) Now glue the roof vapor barrier to the upper side of the roof base, all the way to under the

trimming that runs around it.

e) Remove the covering of the flap driving motor by untwisting the wing nuts and pull the vapor

barrier under the motor covering. Screw the covering on again to provide the motor with a

water-tight seal.

f) Use a crane to transport the exhaust air fan to the roof base; remove the cover plate of the

roof base for the outgoing air. The cover plate is delivered in advance as rain protection.

g) Inside the building, under the roof base for the exhaust air, install a condensate basin for

dripping water, according to the details.

h) Install the T-piece for the suction, with the suction bend, on the outside air roof base.

When installing the roof base, pay attention to the pitch of the roof!

2. Installing the air column

i.Cool AirCenter, Installation of the roof ducts for outside air and exhaust air, pitch of the roof, Installing the air column, Duct installation, Installing the control cabinet,
i.Cool AirCenter, Installation of the roof ducts for outside air and exhaust air, pitch of the roof, Installing the air column, Duct installation, Installing the control cabinet, 


a) Use anchor bolts to fix the supply air outlet to the hall floor. To do this, open the installation

openings in the bottom of the air outlet. Now you can mark the drilling holes on the floor and

screw the air outlet to the floor, using the enclosed anchor.

b) Use a forklift or block and tackle to lift the supply air unit to the supply air outlet; make an

air-tight connection to the supply air outlet with four M-8 screws. If the supply air unit

consists of 2 elements (cooling part + fan part with filter), first put on the cooling piece, then

the fan piece. Connect the two parts to one another in the insides of the devices with the

enclosed clamps. The seal between the supply air outlet and the supply air unit is made with

rubber sealing tape or transparent silicone.

Position the air columns according to the existing detail plans.

When surveying, you must ensure that the dimensions are accurate. You must install

the units in the vertical position.

3. Duct installation

a) Install the ducts between the roof base for the outside air suction and the supply air unit

using ventilation ducts of zinc-coated steel plate with a wall thickness of 1 mm. If you use

an exhaust device instead of roof fans, install the ducts as described above.

b) If the outside air/recirculating air mixing chamber is not integrated in the roof base, insulate

the ducts from the roof base for the outside air to the mixing chamber with diffusion-tight

insulation (such as the Armaflex brand, 9mm).

Refer to the detail plan for the items included in the delivery and the installation arrangement.

4. Installing the control cabinet

i.Cool AirCenter, Installation of the roof ducts for outside air and exhaust air, pitch of the roof, Installing the air column, Duct installation, Installing the control cabinet,


a) Position the switch cabinet according to the existing installation plans. You do not have to

fix it to the floor.

5. Installing the two room temperature sensors

a) Install one room temperature sensor between the last and next-to-last printing unit, at a

height of approximately 2 m (6.5 ft).

b) Install the second room temperature sensor in the area of the folder, at a height of

approximately 2.5 m (8 ft) (install on the operator's side of the printing press, according to

specifications in the installation plan).

You must coordinate the attachments with the machine manufacturer's chief engineer.

6. Electrical wiring

Carry out the electrical wiring according to the existing cable list and the submitted circuit

diagrams.

The supply air units have already been wired to a terminal box on the outside.

Required are:

a) Main incoming supply to i.Cool AirCenter switch cabinet

b) Cable bundle for demands and collect error message between the printing press and the

i.Cool AirCenter switch cabinet

c) Power and control lines between the i.Cool AirCenter switch cabinet and the supply air units

d) Power and control lines between the i.Cool AirCenter switch cabinet and the exhaust air

fans


i.Cool AirCenter, Installation of the roof ducts for outside air and exhaust air, pitch of the roof, Installing the air column, Duct installation, Installing the control cabinet,
i.Cool AirCenter, Installation of the roof ducts for outside air and exhaust air, pitch of the roof, Installing the air column, Duct installation, Installing the control cabinet, 


e) Sensor lines between the i.Cool AirCenter switch cabinet and the two room sensors

f) Manufacture of an analog telephone connection for modem operation (in the i.Cool

AirCenter control cabinet). If an i.Cool AquaCenter is delivered at the same time, the

modem connection is in the i.Cool AquaCenter.

g) Bus between the i.Cool AquaCenter and the i.Cool AirCenter switch cabinet.

7. General information on scheduling sequence

a) Placement of the roof base before the delivery of the printing press, using a crane or

inclined lift, including sealing (by the roofer)

b) Installation of the source air columns with a forklift and scaffolding, after the rough

placement of the printing press, including installation of the exhaust air fan on the roof and

installation of the connecting ducts.

c) Electrical wiring of the i.Cool AirCenter

d) Check of all work performed, using the Www.hvacmep.website System Startup Checklist

e) System startup of the i.Cool AirCenter by a system startup technician from Www.hvacmep.website

 