O P E R A T I N G D E S C R I P T I O N Cool AirCenter
General
Directions
Main
Switch
The main switch is to be switched on before
commissioning commences.
Further functions:
1. Switching off of the complete system in the event of
danger.
2. Switching off when work is being performed on the
electrical installation, or when work is
being carried out inside the control switchboard.
Phase
lights L1 - L2 - L3 (with light prefuse)
In order to operate the system, voltage must be present
in all 3 phases.
Should the supply to a phase fail, the motor protection
overcurrent relays for the drive motors are
actuated and switch the control system to fault.
When the 3 phases are restored, before starting up
again, the motor protection equipment must
be switched to the working position by pushing the
keys.
Control
voltage 220 V and control fuses
For safety reasons the control voltage is produced by
the isolating transformer.
The transformer is protected against overloading and
short circuiting by fuses.
Should the complete control system fail, the fuses
should be checked.
For the control circuit supply air and exhaust air
different fuses are used.
In case of a fault the fuses have to be checked.
Operating
or fault indication
The operating status of each motor that is switched on
is indicated by the control panel. Should
a fault occur in the motor control e.g. through the
actuating of an over current relay or a thermal
contact in the motor winding this is shown as a
blinking signal and written into the alarm list of the
panel.
Control
voltage 24 V
The low voltage that is necessary for the signal lamps
and the PLC-terminal strip is produced by a
power supply. The power supply is protected against
overloading and short circuiting by fuses.
In the event of fault the prefuse on the primary side
and the fuses on the secondary side should be
checked.
Voltage
Supply Axicos
The PLC-station has its own power-supply unit with an
input voltage of 230V. It is protected by
fuses.
Collective
fault signal
The individual fault signals are, as explained, shown
on the control switchboard with the help of
the control panel, and in addition collected in the
PLC-station and given out as a PLC collective
fault signal.
The collective fault signal is wired onto an electric
terminal and is available for further signal
transmission.
Ventilation
Technical Directions
1.
Requirements for the operation of the ventilation system
Before starting operation the following points should
be checked:
All the covers, revision ports and access openings on
the aeraulic equipment must be
hermetically closed.
The control units as well as the covers of all
electrical equipment must be closed.
2.
Filter monitoring
The air filters in the supply air units are monitored
with the help of a differential pressure switch.
As the dirt in the filters increases, the differential
pressure rises so causing the diffential
pressure switch to activate a signal in the PLC
station. This is then passed further on over the
collective fault signal.
Attention is also drawn to the dirtying of the filter
by way of a visual reading instrument. The
filter should
be changed by a pressure difference of approx. 200 Pa.
Control
and regulation in the PLC programme:
Demand
supply air and exhaust air
The system is switched with the control switch to ON /
OFF or READY FOR OPERATION.
Control switch with the positions:
2 = AUTOMATIC / remote control
The supply ventilators and the exhaust air ventilators
are free to operate.
By time clock operation automatic the system will be
switched on and off by way of the
Axicos PLC-Station.
0 = OFF
1 = MANUAL (ON)
The supply air ventilators and exhaust air ventilators
are switched ON directly.
Demand the complete system
a) In the simplest case by way of an external
(potential free) contact of the printing machine.
Result: When the printing machine is running the
ventilation system also functions.
b) In addition to the the printing machine contact, the
ventilation system can be switched on in
combination with the external selector switch. This is
carried out by way of the position
HAND in continuous operation, or the position A ( A =
Automatic), by way of a time
programme contained in the DDC-programme (time
dependent ON / OFF).
Operation:
night cool control
The method of operation is only effective when the
ventilation system from the normal operating
demand is switched to the OFF function.
This auxillary operation is intended for cooling the
warm air in summer time by way of ventilation
operating at night. The low temperature outside air is
used to remove the remaining room heat
caused by daytime working. This results in the room being
cooled down.
The night cooling system switches on under the
following conitions:
Room
temperature in excess of room temperature set point + 3°C
The
difference between inside and outside temperature must be more than 3K
Night
switching time is between 22 p.m. and 6 a.m.
The above conditions are programmed in the PLC-station
, however they can be altered at any
time.
With this auxillary operation the supply air
temperature base, which is dependent upon the room
temperature, is changed over to a low temperature
niveau, to enable ventilation (cooling) with the
highest possible percentage of outside air.
Supply air temperature base by normal operating =
+19...26°C
Supply air
temperature base by night cooling operation = +17…24°C





No comments:
Post a Comment
Please do not enter any spam link in the comment box